Exciter Model: ST4C
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Ta < 0.5*Mult*TimeStep then Ta = 0, ElseIf 0.5*Mult*TimeStep < Ta < Mult*TimeStep then Ta = Mult*TimeStep
- If 0.0 < Tr < 0.5*Mult*TimeStep then Tr = 0, ElseIf 0.5*Mult*TimeStep < Tr < Mult*TimeStep then Tr = Mult*TimeStep
- If 0.0 < Tg < 0.5*Mult*TimeStep then Tg = 0, ElseIf 0.5*Mult*TimeStep < Tg < Mult*TimeStep then Tg = Mult*TimeStep
- Kpm and Kim: Kpm can't be 0 if Kim = 0, if true then Kpm changed to 1.
- Kpr and Kir: Kpr can't be 0 if Kir = 0, if true then Kpr changed to 40.
- If Vrmax < Vrmin then swap the values
- If Vmmax < Vmmin then swap the values
- If Vamax < Vamin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vr > Vrmax, then Vrmax = Vr or if Vr < Vrmin, then Vrmin = Vr
- If Vm > Vmmax, then Vmmax = Vm or if Vm < Vmmin, then Vmmin = Vm
- If Va > Vamax, then Vamax = Va or if Va < Vamin, then Vamin = Va
Model Equations and/or Block Diagrams
Parameters:
| VOS | PSS input: if = 1, add to error signal; if = 2, add after HV gate 1 |
| OEL | OEL input: if < 2, add to error signal; if = 2, LV gate 1; if = 3, LV gate 2 |
| UEL | UEL input: if < 2, add to error signal; if = 2, HV gate 1; if = 3, HV gate 2 |
| SCL | SCL input: if < 2, add to error signal; if = 2, Take Over 2 1; if = 3, Take Over 3 |
| SW1 | Logical switch 1 (1 = Position A, 2 = Position B) |
| Tr | Filter time constant, sec |
| Kpr | Proportional gain, pu |
| Kir | Integral gain, pu |
| Vrmax | Maximum control element output, pu |
| Vrmin | Minimum control element output, pu |
| Kpm | Proportional gain of field voltage regulator, pu |
| Kim | Integral gain of field voltage regulator, pu |
| VmMax | Model Parameters\VmMax |
| VmMin | Model Parameters\VmMin |
| Ta | Voltage regulator time constant, sec |
| VaMax | Maximum exciter output, p.u. |
| VaMin | Minimum exciter output, p.u. |
| Kg | Excitation limiter gain, pu |
| Tg | Feedback time constant of field current regulator, sec. |
| VgMax | Maximum excitation voltage |
| Kp | Potential source gain, pu |
| Ki | Current source gain, pu |
| Xl | P-bar leakage reactance, pu |
| ThetaPDeg | Phase angle of potential source, degrees |
| Kc | Rectifier regulation factor, pu |
| VbMax | Maximum excitation voltage, pu |